MPC-143 Compare

 Main features:

  • Freely chosen interfaces: up to 4 interfaces.
  • Supported interfaces: RS485, RS232, Opto (Kamstrup), Mbus, GSM/GPRS.
  • Discrete inputs: up to 4 devices
  • Analog inputs: up to 3 devices
  • Supported protocols: Modbus RTU, Modbus TCP/IP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, SNTP, IEC60870-5-104:200 and transparent.
  • Special: transparent non-standart protocol data transfer
  • Power: 15-36 VDC (10VA)
  • External battery: outstanding connector for a battery, support gel and acid 12V batteries (with fully charged 7Ah battery device can operate about 72h)

Description
Specification
Usage
Downloads

OVERVIEW

MPC-143 controller is created for data logging and analyzing in a real time. Using GPRS/GSM controller, sends saved data and reports to remote users.
Controller supports most of protocols and interfaces (RS232, RS485, MBUS, Optoeq, Discrete inputs), so it can be used with different brands and models of counters. Our special “TRANSPARENT” data transfer protocol enables controllers to use with practically any device.
Device supports wide range of protocols (and can be extended by our programmers, if you need some special). For data exchange over GPRS/GSM, Ethernet and/or any Serial interfaces, controller uses Modbus TCP/IP, Modbus RTU, IEC60870-5-104:2000, SNTP and other protocols.
Our clients – GAS, Heat, Watering suppliers, Industry companies in EU, Ukraine, Central Asia.

DEFAULT FEATURES

  • Reading data from energy carrier meters;
  • “TRANSPARENT” remote data reading from counters (special manufacturers protocols);
  • Wide range of interfaces: GSM/GPRS, RS232, RS485, Opto, Mbus and Discrete input ports;
  • Independent data log (up to 8MB) with real time stamp;
  • Remote configuration and upgrading possibilities over GPRS/GSM;
  • Galvanically isolated interfaces and power supply;

BENEFIT TO THE CLIENT

  • Economy, because controller does a lot of mechanic work, so your professionals can do more important work;
  • Flexibility, because you can customize hardware and software settings;
  • Increase efficiency, because the data are sent to a central computer continuously. If connection is lost, data will be safe kept in controllers memory, until connection will be reestablished;
  • Increases security, because the relevant information is rapidly shorten response time;
  • Versatile, because this controller can retrieve data from different manufacturers and even different types of meters;
  • Simplicity, because of intuitive control and optimally assembled LED’s it is easy to monitor and maintain equipment;
  • A good partner, because we not only help you customize device and will make equipment, but also flexibly adapt controller, if your demands will change.

CUSTOMIZING DEVICE

The exceptional feature of this device - a flexible hardware and software configuration, it depends on customer needs, you can choose the desired interface and functionality.

Manufacturers code:

At heating substations:

First interface
GSM/GPRS4 band 850/900/1800/1900 MHz
Second interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Optoup to 2 devices(Kamstrup) data transfer interface
MBusup to 8 devices
Third interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Discrete and Analog interfaces
Discrete IN4sink contact
Analogi IN3thermo-resistance (Pt100, Pt1000), voltage or current
Protocols
Modbus RTU
Modbus TCP/IP
IP
ICMP
UDP
TCP
DHCP
PPP
ARP
SNTP
IEC60870-5-104:2000
DynDNS
FTP server
FTP client
DNS client
General
Power15-36 VDC
Galvanic isolation>1000V
Capacity<5VA
Internal battery3,7V 500 mAh
External batterybattery charging current up to 200mA, acid or gel 12V battery (battery is not supplied with device). With fully loaded 7Ah battery can operate about 72 hours.
Regulatory approvals
Electromagnetic compatibilityEN 55022:2010
EN 55024:2010
EN 61000-4-2:2009
EN61000-4-3:2006
EN61000-4-3:2006/A1:2008
EN 61000-4-3:2006/A2:2010
EN 61000-4-4:2004
EN 61000-4-4:2004/A1:2010
EN 61000-4-6:2009
SafetyEN 61010-1:2001
Specification
CPUARM7
Memoryarchive storage 1-8 MB, independant data storage without power about 5 years
LED indication
Status of discrete input, for each port+
Serial ports read/write for each port+
GSM/GPRS modem status+
Programing and updating
RemoteGSM/GPRS
LocallyRS232 or RS485
Physical characteristics
Dimmensions107x128x50 mm
Weight275 g
Mounting typeon DIN32 rail
Safety classIP20
Climate conditions
Operating temperature-30..+60 °C
Storage temperature-40..+60 °C
Humidity range5-95%, non-condensing
Other fuetures
Real time clock+
MBus auto setup+
24 months warranty period+

Similar devices

 

 

 

 

Send to friend

* - Required field
Sender's E-mail *:
Friend's E-mail *:
Message:
Sent…