MPC-134 Compare

Main features:

  • Freely chosen interfaces: up to 4 interfaces
  • Suppoerted interfaces: RS485, RS232, Opto (Kamstrup), Mbus, GSM/GPRS
  • Discrete inputs: up to 16 devices
  • Discrete outputs: up to 8 devices
  • Analog inputs: up to 4 devices
  • Wide choise of Analog inputs (Current, Voltage, Thermoresistance (Pt100, PT1000, NTC), Resistance)
  • Supported protocols: Modbus RTU, Modbus TCP/IP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, SNTP, IEC60870-5-104:200 and transparent
  • Power: 9-36 VDC (10VA)

Description
Specification
Downloads

OVERVIEW

MPC-143 controller is created for data logging and analyzing in a real time. Using GPRS/GSM modem, controller sends saved data and reports to remote users.
Controller supports most of protocols and interfaces (RS232, RS485, MBUS, Opto, Discrete inputs, Discrete outputs, Analog inputs), so it can be used with different brands and models of counters. Our special “TRANSPARENT” data transfer protocol enables controllers to use with practically any device.
Device supports wide range of protocols (and can be extended by our programmers, if you need some special). For data exchange over GPRS/GSM and/or any Serial interfaces, controller uses Modbus TCP/IP, Modbus RTU, IEC60870-5-104:2000, SNTP and other protocols.
Our clients – GAS, Heat, Watering suppliers, Industry companies in EU, Ukraine, Central Asia.

DEFAULT FEATURES

  • Reading data from energy carrier meters;
  • “TRANSPARENT” remote data reading from counters (special manufacturers protocols);
  • Discrete input/output ports;
  • Analog inputs;
  • Independent data log (up to  8MB) with real time stamp;
  • Remote configuration and upgrading possibilities over GPRS/GSM;
  • Wide range of interfaces: GSM/GPRS, RS232, RS485, Opto, Mbus;
  • Wide choise of Analog inputs (Current, Voltage, Thermoresistance (Pt100, Pt1000, NTC), Resistance);
  • Some interfaces are galvanically isolated.

BENEFIT TO THE CLIENT

  • Economy, because controller does a lot of mechanic work, so your professionals can do more important work;
  • Increase efficiency, because the data are sent to a central computer continuously. If connection is lost, data will be safe kept in controllers memory, until connection will be reestablished;
  • Increases security, because the relevant information is rapidly shorten response time;
  • Versatile, because this controller can retrieve data from different manufacturers and even different types of meters;
  • Simplicity, because of intuitive control and optimally assembled LED’s it is easy to monitor and maintain equipment;
  • A good partner, because we not only help you customize and will make equipment, but also flexibly adapt controller, if your demands will change.

CUSTOMIZING DEVICE

The exceptional feature of this device - a flexible hardware and software configuration, it depends on customer needs, you can choose the desired interface and functionality.

Manufacturers code:

First interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Opto(Kamstrup) data transfer interfence
MBusup to 8 devices
Second interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Third interface
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Fourth interface
GSM/GPRS3 band 900/1800/1900 MHz
Discrete and Analog interfaces
Discrete IN16sink contact
Discrete OUT8open collector, >50VDC and >500mA
Analogi IN4resistance, voltage or current, reading 10 times per second
Protocols
Modbus RTU
Modbus TCP/IP
IP
ICMP
UDP
TCP
DHCP
PPP
ARP
SNTP
IEC60870-5-104:2000
DynDNS
FTP server
FTP client
DNS client
General
Power9-36 VDC
Galvanic isolation>1000V
Capacity300mA max
Specification
CPUARM7
Memoryarchive storage 1-8 MB, independant data storage without power about 5 years
LED indication
Power+
Status of discrete input, for each port+
Serial ports read/write for each port+
GSM/GPRS modem status+
Programing and updating
RemoteGSM/GPRS
LocallyUSB, RS232, RS485
Physical characteristics
Dimmensions197x128x50 mm
Weight450 g
Mounting typeon DIN32 rail
Safety classIP20
Climate conditions
Operating temperature-25..+60 °C
Storage temperature-40..+60 °C
Humidity range5-95%, non-condensing
Other fuetures
Real time clock+
MBus auto setup+
24 months warranty period+

Similar devices

 

 

 

 

 

 

 

Send to friend

* - Required field
Sender's E-mail *:
Friend's E-mail *:
Message:
Sent…